The front-panel connector is a visible hardware feature. It does not, by itself, establish which data a Bently Nevada 3500/22M system can capture and deliver to the host software.
A successful connection or a visible vibration value tells you something about communication. It does not tell you whether the system will save a waveform when an alarm occurs—or capture one as machine speed changes.
Identify the Pictured Front-Panel Interface
3500/22M · 138607-01
3500/22M · 288055-01
01Define the Data the Project Must Deliver
“We need vibration data after the replacement” is too broad for a quotation or acceptance plan. Reviewing a trend, investigating an alarm and documenting a startup may require three different records.
| Data required | Capture trigger or context | Evidence to check |
|---|---|---|
| Static values | Current reading or numerical trend | Confirm the measurement, channel and host reading or trend record. Static capture is standard; a visible value is not proof of waveform capture. |
| Steady-state waveforms | Software command, schedule or configured alarm | Check enabled Steady-State Points or Transient Points for the channels, the applicable trigger configuration and a corresponding waveform record. |
| Parameter-change waveforms | Change in a configured parameter, such as machine speed | Check enabled Transient Points, the parameter and trigger configuration, and the resulting waveform in the host record. |
Based on datasheet 161581 Rev. AC, pp. 1 and 8. This table defines procurement and acceptance scope; it is not a commissioning procedure.
02Separate Static Capture from Steady-State Waveform Points
A static value is a numerical result. A trend may show when an overall vibration reading increased, but it cannot replace the waveform an analyst needs to examine that event.
The 3500/22M provides static capture as standard. Steady-State Points are a dynamic-data option associated with the 3500/09 Channel Enabling Disk. They support waveforms collected by software command, schedule or alarm. Specify whether “steady-state data” means numerical trends or actual waveform records. [1, pp. 1 and 8]
03Identify What Transient Points Add
Transient Points include the Steady-State Point functions and add waveform collection triggered by changes in a parameter such as machine speed. An alarm-triggered waveform and a speed-change-triggered waveform are distinct requirements, even if both are collected during the same startup. [1, p. 8]
If the project needs a waveform as the machine accelerates through a specified speed range, a manually requested waveform does not demonstrate that the speed-change trigger works. Define the channels, triggering parameter and record the host must retain.
04Verify Enabling, Host Software and Configuration Evidence Separately
The datasheet lists the front-panel USB-B port separately from dynamic-data enabling and describes Ethernet communication with the host. Matching USB ports and visible values therefore do not establish which waveform points are enabled. [1, pp. 1–2, 4 and 8]
Identify the hardwareWhat is installed?
Verify the enablingWhich points are covered?
Confirm the host recordWas the required data retained?
Hardware
TDI and I/O nameplates, complete part numbers, available revisions and installed monitor list.Enabling
Existing 3500/09 records showing point types and coverage for the required channels.Host and configuration
Software name and version, configured channels and triggers, and a representative host record for each required capture type.An enabling record does not prove a trigger is configured. A configuration screenshot does not prove that the host received and retained the waveform. Record acceptance evidence for each required capture type.
05Include the Data-Capture Scope in the Spare-TDI Enquiry
For a 3500/22M 288055-01 quotation, send Moore Automation Limited the module and I/O nameplates, available hardware and firmware versions, monitor list, host software version and existing enabling records. List the required channels and capture triggers.
Please quote the 3500/22M 288055-01 and identify the I/O module, accessories and documentation included or excluded. We require the channels and capture triggers listed in the attached schedule. State separately what enabling or software, if any, is included and what remains to be verified against our installed system.
Request written confirmation of lead time, warranty, traceability and any required certification documents for the specific offer. Do not assume a hardware quotation includes software or that existing enabling can be transferred.
Source and Scope
[1] Baker Hughes / Bently Nevada, 3500/22M Transient Data Interface Module · 161581 Rev. AC. Accessed 4 November 2026. The document carries a 2025 copyright notice; its exact publication date was not confirmed.
No specific rack, firmware, host software or enabling record was reviewed. This article does not establish interchangeability between 288055-01 and 138607-01.